489-P5-LO-A20 Technical Specifications
| Digital Inputs 489 Sensor Supply | 24 VDC at 20 mA Max |
| Field Breaker Discrepancy Elements | Trip |
| Ground Directional Timing Accuracy | ±100 ms |
| Negative Sequence Overcurrent Time Delay | 0.1 to 100.0 s in steps of 0.1 |
| Neutral Voltage Input Conversion Range | 0.005 to 1.00 × Full Scale |
| Overcurrent Alarm Timing Accuracy | ±0.5% of total time |
| Phase Differential Pickup Level | 1.01 to 1.50 × rated V in steps of 0.01 |
About the 489-P5-LO-A20
489-P5-LO-A20 is a generator management relay that is manufactured by GE Multilin for the 489 series. This relay has 5 A phase CT secondaries. The LO control power is 20-60 VDC and 20-48 VAC at 48-62 Hz. The analog outputs on this relay are 4 to 20 mA. This relay has a basic display.
This unit has a shipping weight of 10 KG (approximate) and has dimensions of 21.6 cm (L) x 22.4 cm (W) x 25.2 cm (H). The front panel includes multiple status LEDs as well as having input buttons, a numeric keypad, an input port, and an LCD screen for reading information at the location of the unit.
The Frequency parameter has a range of 0.00 to 90.00 Hz. The Neutral Volt (3rd) parameter has a range of 0 to 25000 V. The Average Voltage parameter has a range of 0.00 to 1.50 × the rated voltage. The Power Factor parameter has a range of 0.01 to 1.00 lead/lag. The Reactive Power (Mvar) parameter has a range -2.00 to 2.00 x the rated voltage. The Real Power parameter has a range of -2.00 to 2.00 x the rated voltage. The Apparent Power parameter has a range of 0.00 to 2.00 x the rated voltage. The Analog Inputs 1 to 4 parameters have a range of -50000 to +50000. The Tachometer parameter has a range of 0 to 7200 RPM. The Thermal Capacity Used parameter has a range of 0 to 100%. The Current Demand parameter has a range of 0.00 to 20.00 x FLA. The Mvar Demand parameter has a range of 0.00 to 2.00 x the rated voltage. The MW Demand parameter has a range of 0.00 to 2.00 x the rated voltage. The MVA Demand parameter has a range of 0.00 to 2.00 x the rated voltage.
Frequently Asked Questions about 489-P5-LO-A20
Is there a manual for the 489 Series for the GE Generator Management Relays?
How many output relays does the GE Generator Management Relay 489-P5-LO-A20 have?
How often should the 489 generator management relay be powered on?

- What is different between the 489-P5-LO-A20 and a model with an “E” display enhancement rating?
- The “T” models like the 489-P5-LO-A20 come with all the “E” features plus a 10BaseT Ethernet Port.
- What does the “H” stand for in the 489-P5-LO-A20 part number?
- This indicates that this model comes with the harsh environment coating option.
- Is the 489-P5-LO-A20 easy to install/uninstall?
- Yes, the drawout design of this relay makes it super easy to install or uninstall.