Product Description
ABB REF615EA021G HBFCACABNCA1BNN11G is a feeder protection and control IED in ABB Relion® 615 series. It integrates protection, control, measurement, fault recording and supervision functions. It adopts withdrawable plug-in unit design, fully compliant with IEC 61850 standard, supporting GOOSE messaging, fault location, auto-reclosing and optional arc protection. Suitable for radial, looped and meshed distribution networks with or without distributed generation. It can serve as main protection for cable and overhead feeders, or backup protection for transformers and busbars. Configuration and parameter setting are carried out via PCM600 software, widely used in MV substation automation.
Specifications
- Part No.: REF615EA021G HBFCACABNCA1BNN11G
- Series: Relion® 615 Feeder Protection & Control IED REF615
- Protection Functions: Phase overcurrent, instantaneous overcurrent, negative sequence overcurrent, thermal overload, earth fault, multi-frequency admittance sensitive earth fault, reverse power protection, breaker failure protection, fuse failure supervision
- Additional Functions: Fault locator, disturbance recorder, auto-reclosing, synchronism check, circuit breaker condition monitoring, trip circuit supervision
- Communication: IEC 61850 Ed2, GOOSE, IEC61850-9-2 LE, IEC 60870-5-103, Modbus, DNP3
- Time Sync: IEEE1588 V2 PTP
- Analog Input: 3-phase current, 3-phase voltage, residual current/voltage, compatible with conventional CT & VT
- Binary I/O: Programmable DI/DO with flexible signal matrix
- Power Supply: DC 24V / 48V / 110V / 220V; AC 110V / 220V
- Mounting: Panel mount, withdrawable plug-in unit
- Operating Temperature: -25℃ ~ +70℃
- Protection Class: Front panel IP54, unit IP20
- Configuration Tool: PCM600
- Housing: Industrial metal enclosure
Applications
- Main protection for MV overhead lines and cable feeders in utility and industrial substations
- Distributed generation interconnection (solar, wind, self-generation plant) with islanding detection
- Ring main units, switchgears and box transformers for feeder control, auto-reclosing and fault location
- Backup overcurrent and earth-fault protection for transformers and busbars
- Distribution automation for remote measurement, remote signal, remote control and fault report
- Applicable for isolated neutral, resistance-earthed, compensated and solidly earthed power networks
Related Series Models (Relion 615 Series)
REF615, REV615 (Capacitor bank protection), RET615 (Transformer protection), RED615 (Differential protection), REM615 (Motor protection), RER615 (Busbar voltage protection)







There are no reviews yet.