Product Description
LDP1WC-47 is a low pressure monitor of UE Precision Sensors ECHOLINE series. It adopts pure analog circuit without microprocessor, designed for differential pressure monitoring and safety interlock of semiconductor gas cabinet exhaust and ventilation ducts. It supports independent high/low alarm setpoints, with 3.5-digit red LED for real-time pressure display. It has ECHO circuit health self-check output to detect power loss or internal failure. Maintenance mode and adjustable time delay prevent false tripping. Alarm relay is latched and requires manual reset. It is compact, 1/16 DIN panel mount, widely used for fab alarm and exhaust interlock. It is end-of-life and used as spare part for semiconductor and cleanroom automation.
Specifications
- Model: LDP1WC-47
- Brand: UE Precision Sensors (ECHOLINE)
- Type: Low Pressure Monitor
- Media: Dry air, inert non-conductive gas
- Range: 0.2 ~ 20 in WC
- Display: 3½ digit red LED, digit height 0.30 in
- Accuracy: 1% FS @ 20°C
- Alarm Setpoints: High & low independently adjustable, 5%–95% of full range
- Time Delay: 1/10/20/30 seconds, factory default 10s, jumper selectable
- Relay Output: SPDT Form A dry contact, 1A @30VDC resistive, latched alarm, front reset
- Diagnostics: ECHO circuit health output for power loss / internal fault
- Power Supply: 12–24VDC, 1.4W
- Overpressure: ±14.5 psi for ≥8 in WC range; ±80 in WC for below 8 in WC
- Pressure Port: Push-to-connect for 0.25” OD tubing or barbed fitting
- Mounting: 1/16 DIN 43700 panel mount, polycarbonate housing
- Wiring: Plugable terminal block 18–26AWG, 9-pin D-Sub
- Operating Temperature: 0℃ ~ +40℃
- Humidity: 5%–95% non-condensing
- Certifications: UL991, UL508
- Lifecycle: Manufacturer discontinued, industrial spare part
- Weight: Approx. 200g
Application
- Semiconductor fabs: Gas cabinet exhaust differential pressure monitoring & interlock
- Cleanrooms and laboratories: Negative pressure supervision for ventilation
- Pharmaceutical labs & biosafety cabinets
- HVAC duct low differential pressure monitoring
- Exhaust safety interlock, avoid shutdown caused by transient pressure spike
- Spare replacement for legacy ECHOLINE pressure monitors
Related Series Part Numbers
- LDP1WC-NM: Negative pressure variant
- LDP2WC series: Dual channel differential pressure monitors
- LDP5WC series: Higher range pressure monitors
- LDP1WC-xx: Single-channel ECHOLINE monitors with different WC ranges








There are no reviews yet.