Product Description
GE Multilin 889 is an advanced generator protection, control & monitoring IED (Intelligent Electronic Device). Model: 889‑E‑P1‑P1‑B1‑L‑S‑S‑A‑L‑A‑M‑A‑P‑T‑A‑1E‑C‑N‑B‑N‑1. It belongs to GE Vernova Multilin 8‑series platform, featuring draw‑out pluggable hardware design with English language interface. Equipped with P1 current input module and B1 voltage input module, this unit integrates full‑set generator protection, measurement, disturbance recording and programmable logic functions. With high‑end communication hardware and mainstream power‑system protocols, it delivers primary and backup protection for generators and associated unit step‑up transformers, performing fault clearing, condition monitoring and synchronism control for power plant & industrial power station applicationsGE Vernova. It adopts FlexLogic programmable logic, provides comprehensive fault recording, disturbance report and asset monitoring functions. Supported by EnerVista configuration software for commissioning, setting management and post‑fault analysis.
Technical Specifications
- Power Supply: 24‑60 VDC; Typical power consumption 20 W, Max. 34 WManualsLib
- Current Input: P1 module, 1 A secondary rated current
- Voltage Input: B1 voltage sensing module
- Communication (1E): Front USB, rear RS485, dual Ethernet ports; Support Modbus RTU/TCP, DNP3.0, IEC60870‑5‑103/104, IEC61850 Ed.2, OPC UA, IEEE1588 time synchronization; RJ45 copper interfaceGE Grid So…
- Protection Functions: Stator differential, generator‑transformer overall differential, out‑of‑step protection, negative‑sequence overcurrent, ground fault protection, frequency protection, over‑excitation, loss‑of‑excitation, synchrocheck, breaker failure, stator thermal overload, arc‑flash protection and other ANSI standard protection elementsGE Vernova
- Logic: FlexLogic user‑defined programmable logic, virtual I/O, setting‑group selection
- Recording: Fault report, event log, disturbance recording, operating‑hour counter
- Environment: Compliant with IEC60068‑2; Dielectric withstand meets IEEE C37.90; Operating temperature:‑40℃ ~ +85℃ManualsLib
- Mechanical: Draw‑out plug‑in chassis for easy on‑site maintenance & replacement
Product Applications
- Utility power plants: Primary & backup protection for steam turbine generators, hydro‑generators; full‑scope protection for generator‑step‑up transformer unit.
- Industrial captive power plants: Protection & control for gas turbine and diesel generator sets.
- Combined‑cycle renewable power stations: Grid‑tied generator protection, synchronizing control, islanding detection.
- Retrofit & replacement for legacy GE 489 generator protection relays.
- SCADA / DCS integration for remote unit monitoring, trip control and fault data analysis.
- Substation automation deployment complying with IEC 61850 digital substation architectureGE Grid So….
Peer Series Part Numbers
- 889‑E‑P1‑P1‑G1‑H‑S‑N‑A‑L‑N‑M‑A‑S‑F‑C‑SE‑N‑N‑B‑4
- 889‑E‑P1‑P1‑G1‑L‑S‑S‑A‑N‑N‑G‑M‑S‑F‑B‑1E‑C‑N‑B‑N
- 889‑E‑P5‑P5‑B5‑L‑S‑S‑A‑L‑A‑G‑A‑P‑F‑A‑SE‑N‑W‑B‑N‑1
- 889‑E‑P5‑P5‑B5‑H‑S‑S‑A‑L‑A‑M‑A‑P‑F‑A‑SE‑N‑N‑B‑N
- 889‑E‑P1‑P1‑G1‑H‑S‑S‑A‑L‑A‑M‑M‑S‑F‑C‑SE‑N‑N‑B‑4







There are no reviews yet.