GE Multilin F650-N-F-B-F-2-G-0-HI-6E
Complete product profile: Feeder Comprehensive Protection Monitoring Device (Digital Interval Controller)
I. Basic Overview
Brand: GE Vernova (formerly GE Multilin, a well-established power relay protection brand of General Electric, USA)
Full device name: F650 Distribution Feeder Comprehensive Protection Monitoring Device / Digital Interval Controller (Feeder Protection Relay & Bay Controller)
Core purpose: Complete protection for 10kV/35kV substation distribution lines, electrical measurement and control, power metering, fault recording, local / remote automatic interlock control for circuit breakers, widely used in urban distribution networks, plant power supply, rail transit, petrochemical power plants, and station feeder interval monitoring and protection
Life cycle: The original factory has completely stopped production, no new original factory futures available; market supply sources are all original and brand-new inventory spare parts, and refurbished complete machines from disassembly and maintenance (supply status as of 2026)
Detailed Interpretation of the Complete Order Code (F650-N-F-B-F-2-G-0-HI-6E) Table
Segmentation of coding Code Official standard definition
Prefix F650 Product series: Feeder-specific protection and monitoring host
1 N CPU firmware version: Standard feeder complete protection core, integrating overcurrent, grounding, reclosing, and all feeder protection logic against islanding
2 F Human-machine interface: IEC power standard graphic color large screen, capable of drawing primary main wiring single-line diagrams and real-time display of power grid operation parameters
3 B COM1 communication board: Dual redundant RS485 serial ports, Modbus RTU master-slave protocol
4 F COM2 communication board: Redundant plastic optical fiber communication interface, anti-electromagnetic interference, suitable for strong electromagnetic environment wiring in substations
5 2 Local I/O backplane configuration: 8 digital input DI + 6 relay digital output DO + 2 trip circuit break monitoring (to prevent protection malfunction)
6 G Voltage connection standard: Three-phase four-wire 3PT + 3CT universal wiring, suitable for most domestic and overseas power distribution systems
7 0 Expansion I/O slot: No external remote CIO distributed I/O module
8 HI Device auxiliary power supply: Wide-range AC/DC universal power supply
AC 110~230V / DC 110~250V (88~300V full compatibility)
9 6E Hardware & system suffix:
6 = Hardware motherboard version Rev.6; E = English operating system interface, with CE, UL complete set of international industrial safety certifications

Core hardware electrical parameters
Power consumption: Static power consumption of the entire machine ≤ 12W
Switching quantity points: 8 digital input DI without remote signal, 6 digital output DO for normal outlets + 2 trip circuit break monitoring (to prevent protection malfunction)
Communication interfaces
Front panel RS232 debugging port: Compatible with EnerVista software for setting protection values, uploading and downloading fault data
Dual redundant RS485, plastic optical fiber dual-channel communication, supporting Modbus RTU
Optional compatibility with IEC60870-103, IEC61850 power protocol (firmware can be configured)
Structural installation: 1/2 19-inch standard cabinet frame, 6U height, drawer-type plug-in modular structure, convenient for maintenance and replacement
Environmental tolerance: Working temperature -25℃ ~ +55℃; Indoor control cabinet installation, IP30 protection level; Meeting strict EMC electromagnetic compatibility standards of the power industry

Complete protection functions (standard configuration)
1. Line fault main protection
Time-limited / reverse-time phase-to-phase overcurrent, instantaneous overcurrent, voltage locked overcurrent protection
Ground fault, sensitive grounding, directional grounding protection; Four-stage adaptive automatic reclosing (with同期 verification)
Overvoltage, undervoltage, low frequency / high frequency, frequency slip protection
2. Measurement and control with auxiliary functions
Real-time measurement: Three-phase voltage, current, power, power factor, frequency, harmonic, cumulative energy metering
Fault recording: Store 20 sets of fault process waveforms; SOE event sequence record (479 entries with millisecond-level timestamp)
IEC61131-3 programmable logic PLC, can customize bus interlock, automatic backup, load shedding logic
Trip circuit monitoring, CT/PT break alarm, circuit breaker failure protection, arc flash fault detection







There are no reviews yet.