Metso IOP365 is an isolated analog input module for Metso DNA DCS control system, rack-mount hot-swappable card. It features 8 fully isolated analog input channels. Each channel can be software-configured for different current and voltage signals. High voltage isolation between channels and between field side & system side provides strong noise rejection. Equipped with 16-bit high-precision ADC, it supports loop burnout detection and fast sampling rate. It acquires analog signals from field transmitters and sensors and transfers process variables to DNA system controllers. Designed for heavy industrial sites such as mining, pulp & paper and metallurgy with heavy dust and strong EMI, it serves as the core I/O acquisition unit for Metso DNA system.
Specifications
- Model: IOP365
- Brand: Metso (Metso Outotec)
- Type: Isolated Analog Input Module
- System: Metso DNA DCS
- Channels: 8 isolated analog inputs, software configurable per channel
- Supported Signals: 4-20mA, 0-20mA, ±20mA, 0-10V, ±10V, 1-5V
- Isolation Rating: 1500V AC channel-to-channel; 1500V AC field-to-system
- Input Impedance: 250Ω for current; >1MΩ for voltage
- Resolution: 16-bit
- Accuracy: ±0.1% of span (typical @25℃)
- Channel Update Rate: 50ms per channel
- Burnout Detection: Loop fault detection below 3.6mA
- Power Supply: 24V DC ±10%
- Typical Power Consumption: 3.5W
- Surge Protection: 4kV
- Mounting: Rack plug-in card
- Operating Temperature: -20℃ ~ +60℃
- Storage Temperature: -40℃ ~ +85℃
- Relative Humidity: 5%~95%, non-condensing
- Protection Class: IP20 (inside cabinet)
- Weight: approx. 0.6kg
- Certifications: CE
- Features: Fully isolated channels, burnout diagnosis, 16-bit high resolution, hot-swappable, robust EMC immunity
Application
Used in Metso DNA DCS distributed control system to collect 4-20mA / voltage signals from field transmitters for pressure, temperature, flow, level and concentration measurement. Widely deployed in mineral processing, pulp & paper, cement, metallurgy and chemical heavy industries. It transmits field analog signals to DCS controllers for process monitoring, closed-loop regulation and alarm interlock. Isolation protects main control system from ground loop interference, suitable for continuous process control under harsh industrial conditions.
Series Models (Metso DNA IOP Series I/O Modules)
- IOP365: 8-channel isolated analog input module
- IOP364: Analog output module
- IOP308: Digital input module
- IOP309: Digital output module
- IOP330: Pulse counter module
- IOP370: AI module for RTD / thermocouple
- IOP353: Communication interface module