Product Description
Model: HiD2038, Brand: Pepperl+Fuchs, 2-channel SMART Current Driver isolated barrier of H-System HiD2000 series. This module transmits 4-20mA signals from control system to hazardous area to drive SMART I/P converters and valve positioners, supporting bidirectional HART communication. It integrates Line Fault Detection (LFD) to detect open/short circuit of field loop. Safety integrity level up to SIL2 (IEC61508). Bus-powered design, mounted on DIN rail backplane terminal board, compact housing width of only 18 mm. It is a dedicated intrinsic safety barrier for valve driving in hazardous area applications.
Specifications
- Model: HiD2038
- Brand: Pepperl+Fuchs
- Series: HiD2000 H-System
- Channels: 2 channels
- Signal: 4~20mA analog signal, bidirectional HART communication
- Supply voltage: 19~30VDC (bus powered via termination board)
- Power dissipation per channel: 0.85W @24VDC
- Max load resistance: 650Ω
- Signal accuracy: 0.1%
- Safety integrity level: SIL2 (IEC 61508)
- Explosion protection: Intrinsically safe isolated barrier
- Fault detection: Line Fault Detection (LFD), red LED alarm + fault bus output
- Housing width: 18 mm
- Mounting: DIN rail installation with HiD termination board
- Intrinsic safety output parameters: Uo=26.25V, Io=93mA, Po=610mW
- Certifications: IECEx, CE
- Status LED: Green for power; independent red fault LED for each channel
Application
Used in hazardous explosion-prone areas such as oil & gas, chemical, pharmaceutical industries. It transmits 4-20mA+HART signals from safe side to hazardous area for driving SMART I/P converters, valve positioners and solenoid valves. It galvanically isolates safe side and intrinsic safety side, limits energy into hazardous zone for explosion protection. Capable of detecting wire break and short circuit on field loop and sending fault alarm, widely deployed in DCS process control loops.
Same Series Models (HiD2000 Series)
- HiD2037
- HiD2029
- HiD2030
- HiD2061
- HiD2062