Product Description
Schneider PowerLogic ION8800 is a 19-inch rack-mounted high-precision power quality & revenue energy meter, high-end grid monitoring instrument of ION series. It meets IEC 61000-4-30 Class A power quality standard with IEC62053-22 Class 0.2S energy accuracy. Adopting patented ION programmable technology, it detects voltage sags/swells, captures 20μs transients, measures harmonics up to the 63rd order, flicker and symmetrical components. It supports waveform recording, event logging and multi-tariff metering. DIN43862 rack mount with Essailec connector, designed for utility substation revenue metering and power quality compliance monitoring. It has three base variants: ION8800A, ION8800B, ION8800C, expandable with DI/DO, Ethernet, IRIG-B time synchronization and other options.
Specifications
- Model: ION8800 (ION8800A / ION8800B / ION8800C)
- Product Type: Rack-mount Power Quality Analyzer & Revenue Energy Meter
- Metering Accuracy: IEC62053-22 Class 0.2S
- PQ Performance: IEC 61000-4-30 Class A
- Sampling Rate: 1024 samples per cycle
- Harmonic Measurement: Up to 63rd harmonic
- Transient Capture: 20 μs high-speed transient detection
- Measured Parameters: Voltage, current, frequency, active/reactive/apparent power, power factor, energy, flicker, unbalance, symmetrical components
- CT Input: 1A or 5A selectable
- Auxiliary Power: 85~240 V AC; 110~270 V DC
- Power Consumption: Typical 19 VA, Max 32 VA
- Communication: RJ45 Ethernet, RS485; supports Modbus, DNP3, IEC61850; IRIG-B time sync
- Digital I/O: Up to 8 DO, 3 DI (depends on model variant)
- Mounting: 19” rack, DIN43862
- Display: FSTN transflective LCD
- Compliance: IEEE519, EN50160, IEC61000-4-7, IEC61000-4-15, CBEMA/ITIC
Applications
- Power Substations: Busbar revenue metering & feeder long-term power quality monitoring
- Utility Power Grids: Billing settlement, multi-tariff metering, PQ compliance reporting
- Cogeneration / IPP Plants: Grid interconnection point monitoring for power, energy & disturbances
- Critical Industrial Loads: Voltage sag & harmonic monitoring for semiconductor, data center and metallurgy facilities
- Energy Management System (EMS): Energy statistics, demand control, power factor optimization, load shedding
- Metrology Labs: Grid disturbance recording, transformer loss evaluation, PT/CT instrument transformer correction
Series Models
ION8600, ION7550, ION7650, ION7400, PM8000