Product Description
Triconex HD8311 (formerly Invensys, now Schneider Electric) is a high-density power supply module for Tricon TMR triple modular redundant SIS safety instrumented systems. It powers Tricon main chassis, expansion chassis and remote expansion RXM chassis. The module accepts 24 VDC input and converts it to internal logic voltage to supply TMR processor cards and high-density I/O modules. Equipped with self-diagnosis, over-current, over-voltage and over-temperature protection. It supports hot swap and dual redundant power configuration, designed for high safety integrity level applications such as ESD emergency shutdown and F&G fire & gas systems. It meets industrial safety certifications to guarantee safe continuous operation for critical processes in petrochemical, oil & gas and power plants.
Specifications
- Model: HD8311
- Brand: Triconex (Schneider Electric)
- Product Type: High Density Power Supply Module
- Input Voltage: Nominal 24 VDC, range 22~31 VDC
- Output: Internal logic power for Tricon backplane
- Input Fuse: 15 A time-delay fuse
- Output Hold Time: Min 2.8 ms
- Max Power Rating: 175 W
- System Architecture: Compatible with Tricon TMR triple modular redundant system, supports dual redundant power supply
- Protection: Overvoltage, overcurrent, overtemperature, short circuit protection, built-in fault diagnosis
- Mounting: Chassis slot mount, hot-swap replaceable online
- Operating Temperature: 0℃ ~ +60℃
- Galvanic Isolation: ≥1500 VDC
- Weight: Approx. 2.7 kg
- Applicable Chassis: Tricon main chassis, expansion chassis, RXM remote expansion chassis
Applications
- Petrochemical & Refinery: Power supply for SIS safety instrumented systems and ESD emergency shutdown systems
- Natural gas & offshore oil platforms: Fire & Gas (F&G) safety protection systems for critical process safety
- Thermal / gas power plants: Safety interlock protection for boilers and steam turbines
- LNG terminals & coal chemical plants: High-reliability triple redundant safety control systems
- Pharmaceutical & fine chemical plants: Process interlock and emergency shutdown SIS
- Critical industrial facilities: DCS & SIS integrated projects, redundant power expansion for safety systems
Series Models
8300A, 8310, 8311, 8312, 8321, 8314, 8315







There are no reviews yet.