Basic Information
Main IED Model: RED670 (Relion®670 Series Line Differential Protection IED) I/O Board Part Number: 1MRK002133‑ABR02 Board Type: 8‑Channel Binary Output Module (BOM), SPDT‑C relay contacts Application: EHV/HV overhead & cable transmission lines; 2‑terminal up to 5‑terminal line differential protection, widely deployed in power transmission substationsManualsLib.
Key Board Specifications:
- Output Channels: 8 independent relay outputs, SPDT Form‑C (1NO+1NC)
- Contact Rating: 2‑5A @30VDC /250VAC resistive load; intermediate relay recommended for trip circuits
- Isolation: Min. 2.5kV AC galvanic isolation between logic bus and field contacts
- Response Time: Typical 10‑15ms, max ≤20ms
- Power Supply: 24VDC from backplane bus
RED670 Main Unit:
- Analog Inputs: Up to12 universal AI channels (current / voltage)
- Communication: Dual Ethernet IEC61850 (GOOSE/MMS), DNP3, IEC60870‑5‑103, SPA, LON; IEEE C37.94 fiber for differential linkManualsLib
- Configuration Tool: PCM600
- Operating Temperature: ‑25℃ ~ +70℃
- Lifecycle: RED670 main unit and 1MRK002133‑ABR02 board are discontinued by OEM. Surplus new, used and refurbished spare parts available.
Main Protection Functions of RED670
- Line differential protection 87L (3CT /6CT configuration, up to 5‑terminal line)
- Distance protection 21, quadrilateral / mho characteristics, suitable for series‑compensated lines
- Phase overcurrent 50/51, directional overcurrent 67
- Earth‑fault & directional earth‑fault protection 50N/51N,67N
- Circuit‑breaker failure protection 50BF, pole‑discrepancy protection
- Over‑voltage / Under‑voltage 59/27, frequency protection 81, out‑of‑step protection
- Auto‑reclosing 79, fault locator, broken‑conductor detection
Monitoring & Recording
- COMTRADE format disturbance recorder, Sequence of Event Recorder (SER)
- Circuit‑breaker condition monitoring, trip‑circuit supervision
- Electrical measurement, fault location function
Compatibility Notes
- Exact part number 1MRK002133‑ABR02, hardware revision ABR02. Compatible with Relion 650 / 670 family IEDs (RED670, REF670, RET670, REB670) in I/O extension racks; NOT compatible with 615/620/630 series devices.
- Verify hardware revision for replacement. Different hardware revisions are not freely interchangeable; channel test required after replacement.
- RED670 firmware version must match project configuration files.
- This board provides only output I/O functions; protection logic resides on CPU main board.
Procurement Notes
- Distinguish full IED RED670 versus I/O board 1MRK002133‑ABR02. 1MRK002133‑ABR02 is merely output board, not complete protection relay.
- Confirm full part number and hardware revision for spare parts; inspect backplane connector and relay contact condition.







There are no reviews yet.