Basic Information
Full Order Number: 3BHE035301R0003 Model: UNITROL1010 BASIC Product Series: UNITROL 1000 Device Type: Compact Digital Excitation Regulator (Automatic Voltage Regulator, AVR) Application: Medium‑small brushless synchronous generators, for captive power plant, gas/diesel generator sets, marine power station, small hydropower, synchronous wind turbine units.
Excitation Output: Continuous excitation current 10A DC @55℃; 10s short‑time overload 25A DC Voltage Regulation Accuracy: ±0.5% Auxiliary Power Supply: AC 9‑300V / DC 18‑420V, wide AC/DC input Operating Frequency: 25‑600Hz, support 50Hz /60Hz and variable‑speed units I/O Configuration: 8 Digital Inputs, 4 Digital Outputs; 3 Analog Inputs, 2 Analog Outputs Communication Interfaces: Ethernet (Modbus TCP), USB, RS485 Commissioning Software: CMT1000 Operating Temperature: ‑40℃ ~ +70℃ Protection Class: IP20 Certifications: CE, UL, DNV marine certification Lifecycle: Within OEM service period; new original spare parts available, second‑hand and refurbished units also available on market.
Main Control Functions
- Automatic Voltage Regulation (AVR)
- Field Current Regulation (FCR)
- Power Factor (PF) control, Reactive Power (VAR) control; bumpless transfer between modes
- Reactive load sharing for parallel generator operation
- Auto‑synchronization and voltage matching
- Rotating Diode Monitoring
- Multiple limiters: max/min field current limiter, V/Hz limiter, PQ limiter, stator current limiter
Monitoring & Recording Functions
- Event recorder & data logger with time stamp
- Excitation system fault diagnosis and alarm output
- Real‑time monitoring of generator voltage, field current, reactive power and power factor
Compatibility Notes
- Full order number 3BHE035301R0003 (BASIC version); Distinguish from LIGHT version 3BHE035301R0002. Firmware function packages cannot be interchanged.
- Successor hardware UNITROL1020 (rated excitation current 20A), same dimension and interface with higher output capacity.
- Drop‑in replacement for legacy UNITROL1000‑7 BASIC.
- Parameter file must match firmware version; re‑download project parameters is recommended after module replacement.