Foxboro H90‑QNVD044L0 pneumatic positioner valve

Brand/Manufacturer:Foxboro

Order Number: H90‑QNVD044L0

Country of Origin: USA

Condition: Original Brand

Lead Time: Available in stock

Payment Term: 100% TT In Advance

Tag:

Product Description

Foxboro H90‑QNVD044L0 (Eckardt legacy under Schneider Electric), Analog Electro‑Pneumatic Valve Positioner, member of discontinued H90 series non‑smart positioner. It receives 4‑20 mA analog control signal from DCS/PLC and converts to pneumatic output for single‑acting pneumatic actuators. Adjustment via potentiometers and dip‑switches; no digital communication. Local mechanical travel indicator. Die‑cast aluminium housing with intrinsically‑safe explosion‑proof approval for petro‑chemical hazardous areas. Available supplies are new surplus stock and fully‑tested refurbished units. 
Model code breakdown H90‑QNVD044L0

‑ H90: H90‑series analog electro‑pneumatic positioner

‑ Q: Single‑acting output

‑ N: NAMUR mounting interface

‑ V: Intrinsically‑safe Ex ia IIC T6

‑ D: 4‑20 mA DC input signal

‑ 044: Supply air pressure range 1.4‑4.0 bar

‑ L0: Version without position transmitter output

Technical Specification

Item Specification
Full Model H90‑QNVD044L0
Product Type Analog Electro‑Pneumatic Valve Positioner (non‑smart)
Input Signal 4‑20 mA DC, max. loop load 600 Ω
Output Action Single‑acting pneumatic output
Supply Air Pressure 1.4‑4.0 bar (20‑58 psi), clean dry instrument air
Stroke Compatibility Linear:3‑100 mm; Rotary:0‑90°
Air Port Thread 1/4‑NPT
Housing Material Die‑cast aluminium
Ingress Protection IP65 / NEMA 4
Explosion‑proof Ex ia IIC T6, ATEX / FM intrinsic safety
Adjustment Potentiometer & dip‑switch; No HART / fieldbus
Position Indication Local mechanical pointer; NO 4‑20 mA feedback output
Operating Ambient Temp ‑40℃ ~ +80℃
Storage Temperature ‑45℃ ~ +85℃
Steady‑state Air Consumption 0.12 m³/h
Mounting Standard NAMUR IEC60534‑6 for linear & rotary actuators
Weight Approx. 2.7 kg
Country of Origin Germany (Eckardt)

Product Application

  1. Petro‑chemical, oil‑gas hazardous‑area field service, matched with single‑acting diaphragm / piston control valves.
  2. Converts 4‑20 mA analog signal from DCS/PLC to pneumatic output for precise valve‑stroke control.
  3. Flow, pressure, level and temperature control loops; legacy analog control systems.
  4. Spare‑part replacement for decommissioned plants; intrinsic‑safety hazardous‑location service.

Related & Retrofit Models

‑ H90‑QNVD044L1: Variant with 4‑20 mA position‑transmitter output

‑ H90‑DNVD044L0: Double‑acting H90 positioner

‑ SRI986: Later analog positioner, also discontinued

‑ SRD991‑BHNS7EA4NR: Foxboro smart HART positioner, modern retrofit solution




    Customers reviews

    There are no reviews yet.

    Be the first to review “Foxboro H90‑QNVD044L0 pneumatic positioner valve”

    Your email address will not be published. Required fields are marked *

    If you are interested in our products, or if you have trouble finding the part you need, please feel free to contact us!

    If you are purchasing these items, please let us know the part number and we will be happy to provide you with detailed information and prices. If you have prices from other suppliers, we are also willing to refer to you for discounts. You are welcome to call or email to inquire about prices and delivery dates! Free Online Quotes Email:cxdcs@foxmail.com  Whatsapp/Mobile:+86 13328779317

    Copyright © 2025-2027 shanxi runsheng import and export Co.,Ltd. all rights reserved.

    Search for products

    Back to Top
    Product has been added to your cart
    email: cxdcs@foxmail.com