Product Description
TMG740-3 is an industrial burner control unit from Honeywell (Satronic). It provides sequence control and flame safety supervision for forced draught single-stage / two-stage dual fuel oil/gas burners. It also supports multi-stage or modulating burners and direct air heaters. It works with ionisation probes, UV or IR flame detectors. It integrates full sequence logic including pre-purge, ignition, flame monitoring and flame-fail safety lockout. It latches on fault and requires manual reset. TMG740-3 is drop-in interchangeable with legacy TMG740-1 and TMG740-2, widely used as safety spare for boilers and industrial furnaces.
Specifications
- Model: TMG740-3
- Brand: Honeywell (Satronic)
- Type: Burner Control Box / Flame Safety Controller
- Supply Voltage: 220–240VAC, 50/60Hz
- Power Consumption: Approx. 15VA
- Max Terminal Output Current: 4A per output, total 6A
- Fuse: 10A fast / 6A slow
- Flame Sensing Options: Ionisation, UV, IR
- Flame Sensitivity: Ionisation 1.6µA; UV 70µA
- Typical Ignition Safety Time: 5s (mod dependent)
- Enclosure Rating: IP40
- Operating Temperature: -20℃ ~ +60℃
- Matching Socket: TMG70205
- Compatible Flame Detectors: UVZ780, IRD820, IRD1020
- Standard: EN298
Application
For forced draught gas, oil and dual-fuel burners. Applied on steam boilers, hot water boilers, thermal oil heaters, direct-fired air heaters and heat-treatment furnaces. It executes furnace pre-purge, ignition valve control and continuous flame supervision. It cuts fuel supply and locks out immediately on flame loss to avoid explosion risk. Commonly used in heating, printing & dyeing, food, chemical and coating industries for burner maintenance and spare replacement.
Sibling Series Models
TMG740-1, TMG740-2, TMG720, TMG750, DKG972, TFI812








There are no reviews yet.