National purchasing consultation hotline+86 13328779317

ProSoft MVI56E-61850C Communication Module

Brand/Manufacturer:ProSoft 

Order Number:MVI56E-61850C

Country of Origin: Sweden

Condition: Original Brand

Lead Time: Available in stock

Payment Term: 100% TT In Advance

Tag:

ProSoft MVI56E-61850C Communication Module Comprehensive Description
I. Basic Positioning
MVI56E-61850C = ControlLogix Rack-specific IEC61850 Client (Client) Communication Module
Produced by ProSoft, directly inserted into the backplane slot of Rockwell 1756 ControlLogix PLC/PAC, its function is to enable the AB control system to directly connect to all IEDs (protection relays, measurement and control devices, power quality monitoring equipment) in the intelligent substation that follow the IEC61850 standard.
Suffix Differentiation:
C = Client: PLC actively collects IED data and issues remote control instructions
S = Server: PLC provides data externally in the form of 61850 to the dispatching / comprehensive protection system

Core Communication Capabilities (IEC61850)
MMS Message Specification
Supports BRCB with buffered reports and URCB without buffered reports, receiving active transmission of IED telemetry, telemetry, and alarm events in real time
Supports remote control operations: direct / selective operation (SBO), configurable for normal / enhanced safety mode to issue control, remote adjustment instructions
GOOSE General Object-Oriented Substation Event
Supports GOOSE subscription (receiving trip / interlock signals) + GOOSE publication (PLC sends interlock instructions to the outside)
Maximum 8 GOOSE channels can be published by a single module; each IED can subscribe to a maximum of 4 GOOSE channels, with millisecond-level rapid interlock tripping
Access Capacity
Up to 40 61850 server IED devices can be connected
The maximum mapping of 20,000 data points (Tags) can be achieved for all modules, with a maximum of 500 points per IED
Network Redundancy
Dual Gigabit Ethernet ports, support PRP parallel redundancy protocol, dual networks operate independently, single network disconnection does not interrupt communication, meeting the high availability requirements of power substations
Precise Time Synchronization
Supports IEEE C37.238-2017 Power PTP Precise Time Protocol
Configurable for normal clock / boundary clock mode, unified time for all IEDs in the station, ensuring the accuracy of SOE event sequence recording and fault recording timestamp

Hardware and PLC Compatibility Parameters
Installation: Local / Remote Rack Backplane Installation of ControlLogix, exchanging data through the backplane with the Logix processor
Power Consumption: Approximately 24W
Operating Temperature Range: Industrial-grade wide temperature, suitable for harsh environments in distribution rooms / substations
Backplane Communication: Class1 predefined connection, input maximum 500 bytes, output maximum 496 bytes
Programming Software: Studio 5000 / RSLogix5000, comes with dedicated UDT for custom data types, module data directly mapped to PLC controller tags, no need for complex MSG programming

Companion Configuration and Diagnostic Software
Configuration Manager Configuration Manager
Import IED’s ICD/SCD substation model files, match data models, data reference paths
Configure MMS polling cycle, report control blocks, GOOSE’s GoID/APPID, remote control permissions, PRP network parameters, PTP clock
Diagnostics Tool Diagnostic Tool
Online viewing of network messages, IED online status, communication packet loss, GOOSE subscription anomalies, event error reporting The operational logs can be exported for troubleshooting.
The module is equipped with 4 status LED indicators, which clearly display the module’s operation, network link, and fault alarms.

Typical Application Scenarios
Power plant / substation plant power monitoring: AB ControlLogix collects data from the integrated protection and measurement units of high-voltage switch cabinets.
Intelligent station renovation project: The original AB old control system is connected to the newly built IEC61850 secondary equipment.
Power interlock control: The PLC quickly receives protection trip signals through GOOSE and outputs equipment linkage and locking.
Energy management system: Collects currents, voltages, powers, switch positions, and fault alarms of multiple lines.




    Customers reviews

    There are no reviews yet.

    Be the first to review “ProSoft MVI56E-61850C Communication Module”

    Your email address will not be published. Required fields are marked *

    If you are interested in our products, or if you have trouble finding the part you need, please feel free to contact us!

    If you are purchasing these items, please let us know the part number and we will be happy to provide you with detailed information and prices. If you have prices from other suppliers, we are also willing to refer to you for discounts. You are welcome to call or email to inquire about prices and delivery dates! Free Online Quotes Email:cxdcs@foxmail.com  Whatsapp/Mobile:+86 13328779317

    Copyright © 2025-2027 shanxi runsheng import and export Co.,Ltd. all rights reserved.

    Search for products

    Back to Top
    Product has been added to your cart
    email: cxdcs@foxmail.com